CABLE SIZE FOR TRANSFORMER SECONDARY

RECOMMENDED SIZE OF CABLES FOR THE SECONDARY SIDE OF TRANSFORMER
Capacity of Transformer         kVA
Secondary current      Amps
Minimum size of neutral earthing conductor          (mm)
Minimum size of PVCAPVC cable            (mm)
63
84
25 x 3
50
100
133.3
25 x 3
95 (2 x 50)
160
213.3
25 x 3
185 (2 x 95)
200
266.6
25 x 3
300 (2 x 120)
250
333
25 x 3
(2 x 185)
315
420
31x3/25x4
(2x300) or (3x135)
400
533
38 x 3
(3x300) or (2x400)
500
666.5
25 x 3
(3x400) or (4x240)
630
840
31 x 6
(4 x 400)
750
1000
50 x 4
Busbar trunking