SIZE OF LT LEADS AND FUSES FOR DISTRIBUTION TRANSFORMERS. | |||||||
Capacity of Transformer kVA | Full load Amps | Fuse wire S.W.G | Size of SC Aluminium LT Cable Area (Sq.mm) | Size of G.I.Pipe to be used. Dia. (mm) | Size of fuse units Amps. | ||
11kV | 433 V | 11kV | 433V | ||||
25 | 1.31 | 33.4 | 38 | 21 | 25 | 100 | |
50 | 2.62 | 66.7 | 33 | 18 or 2 of 20 | 50 | 50 | 100 |
63 | 3.32 | 84.5 | 33.5 | 2 of 20 | 95 | 200 | |
100 | 5.25 | 133.5 | 32 | 2 of 18 or 2 of 16 | 185 | 75 | 200 |
200 | 10.5 | 267 | 26 | 2 of 15 | 2 Circuits | 2 of 75 | 2 of 200 each |
SIZE OF LT FUSES FOR DISTRIBUTION TRANSFORMERS